|
Concrete Testing is needed in the case of new concrete to
ensure that the material that was specified and bought is the same material
delivered to the job site. In the cast of
existing concrete testing is needed to identify possible concrete defects that
may effect the performance of the concrete and any coating or treatment using
concrete as it's foundation. There are a dozen different test methods for
freshly mixed concrete and at least another dozen tests for hardened concrete,
not including test methods unique to organizations like the Army Corps of
Engineers, the Federal Highway Administration, and state departments of
transportation.
Testing Fresh
Concrete
Slump, air content, unit weight and compressive strength tests
are the most common tests.
Slump is a measure of consistency, or relative ability of the
concrete to flow. If the concrete can't flow because the consistency or slump is
too low, there are potential problems with proper consolidation. If the concrete
won't stop flowing because the slump is too high, there are potential problems
with mortar loss through the formwork, excessive formwork pressures, finishing
delays and segregation.
Air content measures the total air content in a sample of
fresh concrete, but does not indicate what the final in-place air content will
be, because a certain amount of air is lost in transportation, consolidating,
placement and finishing. Three field tests are widely specified: the pressure
meter and volumetric method are ASTM standards and the Chance Indicator is an
AASHTO procedure.
Unit weight measures the weight of a known volume of fresh
concrete.
Compressive strength is tested by pouring cylinders of fresh
concrete and measuring the force needed to break the concrete cylinders at
proscribed intervals as they harden. According to Building Code Requirements for
Reinforced Concrete (ACI 318), as long as no single test is more than 500 psi
below the design strength and the average of three consecutive tests equals or
exceed the design strength then the concrete is acceptable. If the strength
tests don't meet these criteria, steps must be taken to raise the average.
Moisture
It is generally accepted that concrete should be allowed to
cure a minimum of 28 days before traditional coating materials are applied to
it, with the exception of cementitious coatings that water cure together with
the concrete. This cure duration is based on the time it normally takes for the
concrete to achieve sufficient physical strength to allow various trades to
perform their work without damaging the concrete. Although it is a
civil/structural requirement, the 28-day cure period has been generally accepted
as a limiting factor for the coating of concrete as well. Even after the 28-day
waiting period, moisture may still be present in the concrete. All initial water
in the concrete mix may not have fully reacted, or the concrete may have
absorbed additional water from rain or other sources. This water can migrate to
the surface and affect the adhesion of coatings.
In concrete slabs in areas of high water tables and/or without
the use of proper fill without a vapor barrier under the slab may allow moisture
mitigation to the surface. In most applications this is either unnoticed or of
minimal impact. If however a sealer, coating, or resurfacer is applied this may
become an issue. In the United States, most floor coating manufacturers require
concrete floors to reach a water vapor emission rate of either 3 or 5
pounds/1,000 square feet/24 hours before application as measured by calcium
chloride tests before coating can commence. The time needed to reach the desired
rate varies significantly, ranging from a few weeks to many months.
Moisture Tests
ASTM F 1869 Anhydrous Calcium Chloride
A Petri dish of Calcium Chloride is weighed and placed under a 12”x12” plastic
cover for 48 to 36 hours. After this period the dish is weighed again and based
on the amount of weight gained in water vapor moisture the emission rate of the
concrete can be determined.
ASTM F 2170-02 Probe Test for determining relative humidity
The use of a moisture meter with the use of two sharpened electrical probes that
must be gouged into the surface can determine the percentage of moisture content
in the surface based on the concrete’s ability to conduct electricity.
ASTM D 4253 Plastic Sheet
Commonly referred to as the poor man’s moisture test the plastic sheet test is
simply taping a 12”x12” inch section of plastic sheeting to the slab for 24
hours and visually checking for moisture.
ASTM F 1869 Anhydrous Calcium Chloride
A Petri dish of Calcium Chloride is weighed and placed under a 12”x12” plastic
cover for 48 to 36 hours. After this period the dish is weighed again and based
on the amount of weight gained in water vapor moisture the emission rate of the
concrete can be determined.
ASTM F2170.02 Radio Frequency Method
The most recent development and most accurate in determining relative humidity
directly in concrete slabs is use of radio frequency. This is done both
non-destructively and instantaneously.
Concrete Coating
Test Checklist
- Substrate Temperature
- pH of Substrate
- Sulfate Residue Testing
- Tensile Strength of Concrete
- Bond Strength of Existing Coatings
- Moisture Content of Concrete Substrate
- Dew Point
- Relative Humidity
- Ambient Temperature Range
- Abrasion Resistance Analysis
- Chemical Exposure Requirements
- Skid Resistance Requirements
HOME | SITE MAP |
COAT CONCRETE |
CONCRETE BASICS |
PREP | CONCRETE POLISHING
RESINS |
CONTRACTORS |
RESIDENTIAL INFO |
INDUSTRIAL PHOTOS |
RESIDENTIAL PHOTOS

Vanguard Concrete Coating
3030 Hillcroft SW
Grand Rapids, Michigan 49548
Phone: 616-742-1540
Fax: 616-742-3793
Ian@vanguardconcretecoating.com
© Copyright 2010-13. All
rights reserved by Vanguard Concrete Coating of Grand Rapids, MI. For residential floors our service area includes the Central, Southwest, & West
Michigan cities of Grand Rapids, Muskegon, Traverse City, Mount Pleasant, Midland, Bay City, Saginaw, Flint, Howell, Jackson, Lansing, Kalamazoo, South
Haven, Holland, Grand Haven and small cites in-between. For industrial &
commercial clients we service a larger area including Detroit & Ann Arbor, Ohio / OH,
Northern Indiana / IN, and Northeastern Illinois / IL cities.

Website
Design Company
Grand Rapids, Michigan
|